  "dataset": "ESIF measured replay",
  "file": "assets/data-center/esif-week.json",
  "sha256": "8ab1e558deba88e1a6807b43c8796eb5f8a5795170c7e6ec308eba1525b41621",
  "rows": 10082,
  "weatherRows": 10091,
  "windowSamples": 10080,
  "source": {
    "title": "NLR HPC Facility Power Usage Effectiveness (PUE) Data",
    "authors": [
      "Struan Clark",
      "Justin Strelka"
    ],
    "catalog": "https://data.nlr.gov/submissions/300",
    "doi": "10.7799/3015212",
    "credit": "DOE/NREL/ALLIANCE; dataset published by National Laboratory of the Rockies",
    "retrieved": "2026-10-22",
    "inputSha256": {
      "power.parquet": "19cd12405dde9144b1a360e8c8418666c399a3d0d15a7f846880d71ab22f9dd4",
      "weather.parquet": "97b424993fa77a15117fb2c4659a2c327fc83280f943fab47d9036260289a6a0",
      "README.md": "f69d32f1af598c48a899d54d48b26def2ca78a0c11d848516169570ecae4c029",
      "LICENSE.html": "24768d4c58eb513d63422cdd54479e2ec88d272651d66262f6f2debed75ca74b"
    },
    "reader": "pyarrow==21.0.0",
    "inputURLs": {
      "power.parquet": "https://data.nlr.gov/system/files/300/1757103411-esif.influx.buildingData.PUE.combined.parquet",
      "weather.parquet": "https://data.nlr.gov/system/files/300/1757105566-esif.influx.buildingData.outside.combined_2.parquet",
      "README.md": "https://data.nlr.gov/system/files/300/1769711385-README.md",
      "LICENSE.html": "https://data.nlr.gov/node/300/license"
    }
  },
  "method": {
    "samplingAssumption": "Reported power is treated as point samples. Publisher does not specify sensor averaging or aggregation windows.",
    "powerToEnergy": "Piecewise-linear power interpolation and trapezoidal integration; only valid intervals <=90 seconds. No extrapolation; excluded time remains uncovered.",
    "periodPUE": "Integrated five-component facility energy / integrated IT energy over identical valid intervals. Never the arithmetic mean of sample PUE.",
    "weather": "Most recent same-facility source-clock observation at or before power time, maximum age 90 seconds. Clock alignment is unverified.",
    "heatReuse": "energy_reuse and ere are preserved only as raw fields. Their units/definitions are insufficiently documented for derived heat-recovery claims.",
    "scene": "Authored room and equipment geometry. Facility totals are not disaggregated into invented rack measurements."
  },
  "licenseFile": "assets/data-center/publisher-notice.txt"
}